Knowledge Search
Download document () of 20

PDU3MV6H50

Eaton Tripp Lite series metered outlet PDU, 3PH, 0U, CS8365 input, 12.6kW, 40A, 208V, 36 Outlets (36) C13 (6) C19

General specifications

Product Name
Eaton Tripp Lite series metered outlet PDU
Catalog Number
PDU3MV6H50
UPC
037332163868
Product Length/Depth
2.65 in
Product Height
70 in
Product Width
2.2 in
Product Weight
14.49 lb
Compliances
RoHS
FCC Class A
TAA Compliant
Certifications
NOM
UL 62368-1
RETIE

Product specifications

Form factor
0U (Vertical)
Package contents
  • Local Metered PDU with pre-installed mounting buttons
  • Cord retention brackets
  • Spare installation buttons (2 9mm / 4 6mm)
  • Rack mounting brackets
  • Owner's manual
Operating Temperature
32° to 104°F (0° to 40°C)
Mounting direction
Vertical
Material
Metal
Input connection
HUBBELL CS8365C 50A
Cord length
6 ft
Amperage Rating
35A
Electric current - max
35
Phase
3-Phase
Frequency rating
50/60 Hz
Number of Outputs C13
36
Number of Outputs C19
9
Features
Flex Center
Front Panel LCD Display
Set of 3 digital current meters report current in amps for each output phase
Output Receptacles
C13
C19
Overload protection
Three 20A circuit breakers, 1 per outlet bank
Recommended electrical service
Three-phase 50A 208V service
Reported load Segments
Supports local monitoring of current for each output phase (20A balanced max per L1-L2, L2-L3 and L3-L1); Outlets are color-coded and labeled for phase and load bank identification; L1-L2 feeds black outlets; L2-L3 feeds dark-gray outlets; L3-L1 feeds light-gray outlets
Receptacles
  • C13
  • C19
Input Cord Length
6 ft
Product Features
TAA Compliant
Amperage Rating Details
Agency de-rated to 35A continuous
Operating elevation
0-10000 ft. (0-3000 m)
Operating temperature range
32° to 104°F (0° to 40°C)
Output nominal voltage
208V
Relative humidity
5% to 95% non-condensing
Form Factors Supported
Vertical rackmount installation supported with included mounting brackets; supports toolless mounting in button-mount compatible racks
Output Capacity Details
12.6kVA (208V) total capacity; 20A max per breakered outlet bank; 16A max per C19 outlet; 12A max per C13 outlet
Storage temperature
-22° to 140°F (-30° to 60°C)
Product Highlights
45 208V outlets total (36 C13, 9 C19)
Reports load current per-phase via set of 3 built-in current meters
Toolless button-mount installation; cord retention brackets included
Federal Trade Agreements Act / TAA Compliant for GSA Schedule purchases
Local Metered 12.6kW 3 Phase 208V PDU; 70 in. / 178cm 0U vertical rackmount
Hubbell CS8365C 50A (3P+E) 208V 3 phase input; 6-ft. (1.83 m) line cord
PDU Plug Type
HUBBELL CS8365C 50A
PDU Type
Local metered
PDU Input Voltage
208
PDU Form Factor
Vertical (0U)

Export product specification

Need product support?

Support from Eaton